Temporary Service | 3/9/2005 | 3/9/2005 | 3/9/2005 | P | PASS |
Pat Lass
|
|
|
1:15 pm. ###-####.Scheduled by a contractor via Hello! on 3/9/2005 at 9:30:59 AM. Contact: ###-####. 3/9/2005 9:57:10 AM
T/S U/G Ok
breaker will be changed to coordinate with interupt rateing fault current 3/9/2005 1:17:52 PM
|
Temporary Service | 3/4/2005 | 3/4/2005 | 3/4/2005 | P | FAIL |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 3/4/2005 at 11:16:16 AM. Contact: ###-####.
check fault current.
raintingt enclouser for transformer
2/0 ground for parallel 500kcm
seal unused opening 3/4/2005 3:28:33 PM
|