Final | 5/6/2005 | 5/6/2005 | 5/6/2005 | P | PASS |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla
|
Rough-In Permanent Service | 3/22/2005 | 3/22/2005 | 3/22/2005 | P | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla correction made
p/s o/h n ok 3/22/2005 2:55:46 PM
|
Electrical Rough-In | 3/20/2005 | 3/21/2005 | 3/21/2005 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla cor. posted called 300.4 (A)(1)&(D), box fill , bushings where romex enters sheet metal boxes at recess lights outside recepts front and back 3/21/2005 9:00:11 AM
|