Permit Information
Permit NumberELE05-00842
StatusFinaled
Name AMP ELECTRIC
Site Address 12811 W VENTANA CT
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/28/20057/28/20057/28/2005APASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 7/28/2005 at 6:58:53 AM. Contact: ###-####. called contr to put in gnd screw in bath, corrections made. ok to final
Final7/27/20057/27/20057/27/2005PFAIL
DetailsBob Reichert
###-#### (also ###-#### Jamie) 408.4 panel schedule shall fully identify ckts, 314.17(C) nm cable shall be strapped within 8" of box (bath down), 406.5 cover plates shall seat against mounting surface (microwave and walls), 314.25 boxes shall have covers, BCC disposal shall be installed for final, called contr, left corr notice
Electrical Rough-In3/18/20053/18/20053/18/2005PPASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 3/18/2005 at 8:05:01 AM. Contact: ###-####. corrections made, ric ok p/s u/g n ok 3/18/2005 2:14:56 PM
Electrical Rough-In3/16/20053/16/20053/16/2005PFAIL
DetailsBob Reichert
greg; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 314.23(C) rear outside light box shall be securely fastened, 334.80 ampacity of more than 2 nm cables shall be adjusted over panel,300.4(D) cable shall be 1 1/4" from edge of framing member, 314.17(A) boxes shall be replaced where openings knocked out, 210.52(A) recpt shall be installed by front door into living room,BCC all boxes shall be made up, called contr , left corr notice 3/16/2005 2:50:09 PM