Final | 7/28/2005 | 7/28/2005 | 7/28/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 7/28/2005 at 6:58:53 AM. Contact: ###-####. called contr to put in gnd screw in bath, corrections made. ok to final
|
Final | 7/27/2005 | 7/27/2005 | 7/27/2005 | P | FAIL |
Bob Reichert
|
|
|
###-#### (also ###-#### Jamie) 408.4 panel schedule shall fully identify ckts, 314.17(C) nm cable shall be strapped within 8" of box (bath down), 406.5 cover plates shall seat against mounting surface (microwave and walls), 314.25 boxes shall have covers, BCC disposal shall be installed for final, called contr, left corr notice
|
Electrical Rough-In | 3/18/2005 | 3/18/2005 | 3/18/2005 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 3/18/2005 at 8:05:01 AM. Contact: ###-####. corrections made, ric ok p/s u/g n ok 3/18/2005 2:14:56 PM
|
Electrical Rough-In | 3/16/2005 | 3/16/2005 | 3/16/2005 | P | FAIL |
Bob Reichert
|
|
|
greg; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 314.23(C) rear outside light box shall be securely fastened, 334.80 ampacity of more than 2 nm cables shall be adjusted over panel,300.4(D) cable shall be 1 1/4" from edge of framing member, 314.17(A) boxes shall be replaced where openings knocked out, 210.52(A) recpt shall be installed by front door into living room,BCC all boxes shall be made up, called contr , left corr notice 3/16/2005 2:50:09 PM
|