Permanent Service | 3/24/2005 | 3/25/2005 | 3/25/2005 | A | PASS |
Mike Kinnear
|
|
|
Contact person is Todd Stewart.; Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA
p/s o/h reconnect ok 3/25/2005 8:32:57 AM
|
Permanent Service | 3/20/2005 | 3/21/2005 | 3/21/2005 | A | NR |
Mike Kinnear
|
|
|
Todd Stewart; Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA t/w todd derating not done yet they recall it in 3/21/2005 9:22:52 AM
|
Permanent Service | 3/16/2005 | 3/16/2005 | 3/16/2005 | P | CANC |
Jack Frank
|
|
|
harvey; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie see added t/s 3/16/2005 1:51:25 PM
|
Temporary Service | 3/16/2005 | 3/16/2005 | 3/16/2005 | P | PASS |
Jack Frank
|
|
|
t/s o/h rec. ok only,, correction posted to owner no violation to be retained, shall address wiring to range, dryer, water heater, open splices, smaller wiring tapped off of #8AWG without proper overcurrent protection "tap rule"
I allowed t/s with 2 weeks to correct violations , or power may be turned off
old wiring was in plumbing pipe and elbows
|
Permanent Service | 3/15/2005 | 3/15/2005 | 3/15/2005 | P | FAIL |
Mike Kinnear
|
|
|
harvey ###-#### corrections servive shall comply with NEC2005. NEC250 grounding & bonding (boise city code requires 2 ground rods 6ft or more apart.) NEC230 over head service (boise city code requires 2inch mast through roof) NEC all boxes shall be raintight, NEC all wires shall be protected from physical damage. NEC derating for wires in raceways. 3/15/2005 3:25:57 PM
|