DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent Service3/24/20053/25/20053/25/2005APASS
DetailsMike Kinnear
Contact person is Todd Stewart.; Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA
p/s o/h reconnect ok 3/25/2005 8:32:57 AM
Permanent Service3/20/20053/21/20053/21/2005ANR
DetailsMike Kinnear
Todd Stewart; Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA t/w todd derating not done yet they recall it in 3/21/2005 9:22:52 AM
Permanent Service3/16/20053/16/20053/16/2005PCANC
DetailsJack Frank
harvey; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie see added t/s 3/16/2005 1:51:25 PM
Temporary Service3/16/20053/16/20053/16/2005PPASS
DetailsJack Frank
t/s o/h rec. ok only,, correction posted to owner no violation to be retained, shall address wiring to range, dryer, water heater, open splices, smaller wiring tapped off of #8AWG without proper overcurrent protection "tap rule"
I allowed t/s with 2 weeks to correct violations , or power may be turned off
old wiring was in plumbing pipe and elbows
Permanent Service3/15/20053/15/20053/15/2005PFAIL
DetailsMike Kinnear
harvey ###-#### corrections servive shall comply with NEC2005. NEC250 grounding & bonding (boise city code requires 2 ground rods 6ft or more apart.) NEC230 over head service (boise city code requires 2inch mast through roof) NEC all boxes shall be raintight, NEC all wires shall be protected from physical damage. NEC derating for wires in raceways. 3/15/2005 3:25:57 PM