Permit Information
Permit NumberELE05-00855
StatusFinaled
Name TRI-STATE ELECTRIC
Site Address 495 S CAPITOL BLVD
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New: Electrical for new Hampton Inn Hotel and Parking Garage
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/9/20072/9/20072/9/2007APASS
DetailsBob Reichert
ok to final per conversation w/ 425
Final1/29/20071/29/20071/29/2007PPART
DetailsBob Reichert
signed struct card for hotel shell and foundations, will final ltr
Final1/23/20071/24/20071/24/2007APART
DetailsBob Reichert
CONTACT: GREG PACK - RE-INSPECTION, PARTIAL FINAL Phone #: ###-#### left corr notice,BCC-4-05-33(A)(B) all equipment shall be listed by a nationally recognized testing lab, NEC 110.3(A)(1) listed or labelled equipment shall be suitable for installation and use, told 2 weeks to fix or further action will be taken, signed plans, checking on permits, then can do sign-off
Final1/22/20071/23/20071/23/2007APART
DetailsBob Reichert
Contact: Greg Pack - partial final-1st floor Phone #: ###-#### looked at new mech room for fire prot, told contr to find out about jockey pump listing, drip protection over panels, labels, need elev request for inspections
ELE-Aging Inspection1/22/20071/22/20071/22/2007 DONE
DetailsBob Reichert
suc
ELE-Aging Inspection11/20/200611/20/200611/20/2006 DONE
DetailsBob Reichert
suc
ELE-Aging Inspection9/11/20069/11/20069/11/2006 DONE
DetailsBob Reichert
suc
ELE-Aging Inspection7/10/20067/10/20067/10/2006 DONE
DetailsBob Reichert
suc
ELE-Aging Inspection5/9/20065/9/20065/9/2006 DONE
DetailsBob Reichert
project suc
Electrical Rough-In3/8/20063/8/20063/8/2006PPART
DetailsBob Reichert
CONTACT: LYLE DEAN - TEMPORARY OCCUPANCY INSPECTION PLEASE.; Phone #: ###-#### Internet Inspection Request from: Deb McCoy signed t/o card for first 3 floors of parking garage only
Electrical Rough-In3/1/20063/2/20063/2/2006ACANC
DetailsBob Reichert
CONTACT: LYLE DEAN - TEMPORARY OCCUPANCY INSPECTION; Phone #: ###-#### Internet Inspection Request from: Deb McCoy see final
Final3/2/20063/2/20063/2/2006APART
DetailsBob Reichert
CONTACT: LYLE DEAN - TEMPORARY OCCUPANCY INSPECTION; Phone #: ###-#### Internet Inspection Request from: Deb McCoy corrections made for first 3 floors of parking garage. Went to sign t/o card, but no card available.
Conference3/1/20063/1/20063/1/2006PDONE
DetailsBob Reichert
Contact: Shane Korte - Parking equipment portion; Phone #: ###-#### Internet Inspection Request from: Deb McCoy talked about options to segregate class 2&3 wiring from class 1 at parking lot attendant booth
Electrical Rough-In2/28/20063/1/20063/1/2006APART
DetailsBob Reichert
CONTACT: LYLE DEAN - TEMPORARY FINAL FOR FLOORS 1,2 & 3 ; Phone #: ###-#### Internet Inspection Request from: Deb McCoy most corrections done, will fix some attendant items and call back to get t/o
Final2/24/20062/24/20062/24/2006PFAIL
DetailsBob Reichert
CONTACT: GREG PACK; Phone #: ###-#### Internet Inspection Request from: Deb McCoy met contr, left corr notice, 408.4 circuit directory shall be clear, concise evident for each circuit, 358.12(5) emt shall not be used for fixture support, 358.26 there shall not be over 360 degrees bend in emt between pull points,358.30(A) emt shall be securely fastened within 3' of conduit body, 110.12(A) unused openings shall be closed in boxes, 314.25 boxes shall have covers installed, 410.14(B) electric discharge fixtures surface mounted over concealed boxes, unless designed to be supported by box, shall be provided with openings to provide wiring access, 300.3(C)(1) all circuit conductors shall have insulation rating equal to maximum circuit voltage applied to any conductor in enclosure, 400.8(2) flexible cord shall not be run thru walls, 110.2 equipment shall be acceptable only if approved (parking attendant stations), 427.11 pipeline heating equipment shall be installed to avoid physical damage, NOTE: access to 4th floor via stairs shall be prohibited
Final2/24/20062/24/20062/24/2006PFAIL
DetailsPat Lass
see bobs notes
Permanent Service1/10/20061/11/20061/11/2006ACANC
DetailsBob Reichert
contact: Lyle Dean; Phone #: ###-#### Internet Inspection Request from: Deb McCoy wrong permit , they will fix and recall
Electrical Rough-In12/28/200512/28/200512/28/2005PPART
DetailsBob Reichert
Inspection for 1st floor lobby. Contact Lyle Dean ; Phone #: ###-#### Internet Inspection Request from: Shelli Daylong ok to cover walls, elect room anop
Electrical Rough-In12/27/200512/27/200512/27/2005PPART
DetailsBob Reichert
lyle dean; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to cover hall anop, they need to revisit panel locations due to overhead piping interferences
Electrical Rough-In11/4/200511/7/200511/7/2005APASS
DetailsBob Reichert
CONTACT: LYLE DEAN 1ST FLOOR INSPECTION; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok to cover poured in u/g by elect room
Electrical Rough-In11/3/200511/4/200511/4/2005APASS
DetailsBob Reichert
Contact: Lyle Dean - 1st floor inspection; Phone #: ###-#### Internet Inspection Request from: Deb McCoy u/g ok to cover from elect room to sidewalk in 1st floor garage
Electrical Rough-In11/2/200511/3/200511/3/2005APART
DetailsBob Reichert
Please call Lyle Dean if you have any questions.; Phone #: ###-#### Internet Inspection Request from: Shelli Daylong looking at u/g by elect room, nw stairwell for f/a power and lites.
Electrical Rough-In10/12/200510/12/200510/12/2005PPART
DetailsBob Reichert
CONTACT: LYLE DEAN 2ND FLOOR INSPECTION; Phone #: ###-#### Internet Inspection Request from: Deb McCoy 2nd floor ramp ok to cover anop
Electrical Rough-In10/6/200510/7/200510/7/2005APART
DetailsBob Reichert
CONTACT: LYLE DEAN - 3RD FLOOR PARKING GARAGE RAMP INSPECTION; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ramp 3rd fl ok to pour anop
Electrical Rough-In10/5/200510/6/200510/6/2005APASS
DetailsBob Reichert
CONTACT: LYLE DEAN - INSPECTION IS FOR THE 3RD FLOOR.; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok to cover 3rd floor parking deck anop
Electrical Rough-In9/30/20059/30/20059/30/2005PPART
DetailsBob Reichert
CONTACT: LYLE DEAN - INSPECTION ID FOR THE 4TH FLOOR; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok to cover 4th floor garage deck (mark plans next trip, Lyle not here to find plans)
Electrical Rough-In9/28/20059/29/20059/29/2005APART
DetailsPat Lass
CONTACT: LYLE DEAN - INSPECTION ON 2ND FLOOR; Phone #: ###-#### Internet Inspection Request from: Deb McCoy
2nd floor deck r/i complete
Electrical Rough-In9/26/20059/27/20059/27/2005APART
DetailsPat Lass
Scheduled by a contractor via Hello! on 9/26/2005 at 3:06:36 PM. Contact: ###-####.
anop
Electrical Rough-In9/21/20059/21/20059/21/2005PPASS
DetailsWilliam E Thomas
Contact: Lyle Dean - 1st floor re -inspection; Phone #: ###-#### Internet Inspection Request from: Deb McCoy
as noted on prints for slab ok to cover
Electrical Rough-In9/20/20059/21/20059/21/2005ANR
DetailsBob Reichert
Contact: Lyle Dean- Slab rough-in inside building, 1st floor. corner of Myrtle & capitol; Phone #: ###-#### Internet Inspection Request from: Deb McCoy will re-call
Permanent Service9/13/20059/13/20059/13/2005PPASS
DetailsPat Lass
CONTACT: LEON SHEFFIELD; Phone #: ###-#### Internet Inspection Request from: Deb McCoy
Permanent Service9/8/20059/9/20059/9/2005APART
DetailsPat Lass
CONTACT: LEON SHEFFIELD; Phone #: ###-#### Internet Inspection Request from: Deb McCoy
P/S U/G N Ok for power
contractor will insure weatherproof shed to be in place prior to connection.
Conference9/7/20059/8/20059/8/2005APART
DetailsPat Lass
CONTACT: LEON SHEFFIELD; Phone #: ###-#### Internet Inspection Request from: Deb McCoy
talked ab out inclosure for service
Electrical Rough-In9/1/20059/2/20059/2/2005APART
DetailsPat Lass
CONTACT: LYLE DEAN INSPECTION FOR 2ND & 4TH FLOORS; Phone #: ###-#### Internet Inspection Request from: Deb McCoy
Electrical Rough-In8/25/20058/26/20058/26/2005APART
DetailsPat Lass
###-#### Contact: Lyle Dean - rough-in for 3rd and 4th floor s.w. stairs area; Phone #: ###-#### Internet Inspection Request from: Deb McCoy
anop
Electrical Rough-In8/15/20058/16/20058/16/2005APART
DetailsPat Lass
CONTACT: LYLE DEAN - ROUGH-IN ON 2ND FLOOR; Phone #: ###-#### Internet Inspection Request from: Deb McCoy
anop
Electrical Rough-In8/3/20058/3/20058/3/2005PPART
DetailsPat Lass
CONTACT: LYLE DEAN; Phone #: ###-#### Internet Inspection Request from: Deb McCoy
anop
Electrical Rough-In7/15/20057/15/20057/15/2005PPART
DetailsPat Lass
Contact Doug Loomis; Phone #: ###-#### Internet Inspection Request from: Shelli Daylong
sight lighting allong Broad st ok
Electrical Rough-In6/14/20056/14/20056/14/2005PPART
DetailsPat Lass
Please call Lyle Dean with any questions.; Phone #: ###-#### Internet Inspection Request from: Shelli Daylong
4th floor deck anop
Electrical Rough-In5/25/20055/26/20055/26/2005APART
DetailsPat Lass
CONTACT: LYLE DEAN - 2ND FLOOR INSPECTION; Phone #: ###-#### Internet Inspection Request from: Deb McCoy
ANOP
Electrical Rough-In3/29/20053/30/20053/30/2005APART
DetailsPat Lass
CONTACT LYLE DEAN. UNDERGROUND INSPECTION.; Phone #: ###-#### Internet Inspection Request from: Shelli Daylong
Partial U/G 3/30/2005 8:34:43 AM
Electrical Rough-In3/23/20053/24/20053/24/2005APART
DetailsPat Lass
Contact: Lyle Dean - Underground insp. - Please inspect as early as possible; Phone #: ###-#### Internet Inspection Request from: Deb McCoy
6 in duct bank to outside of building ok 3/24/2005 9:08:12 AM
Electrical Rough-In3/15/20053/16/20053/16/2005APART
DetailsPat Lass
Contact: Lyle Dean - Underground Inspection; Phone #: ###-#### Internet Inspection Request from: Deb McCoy
partial u/G ok 3/16/2005 10:31:12 AM