Final | 4/27/2005 | 4/28/2005 | 4/28/2005 | A | CANC |
Bob Reichert
|
|
|
This is for fianal. Please call Dennis with any questions ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa Inspection cancelled from web by: Daniel Gamboa
|
Final | 4/28/2005 | 4/28/2005 | 4/28/2005 | P | PASS |
Bob Reichert
|
|
|
This is fo final inspection call dennis with any questions.573.2679; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa ok to final, signed occupancy card. 4/28/2005 3:09:03 PM
|
Final | 4/27/2005 | 4/27/2005 | 4/27/2005 | P | CANC |
Bob Reichert
|
|
|
Please do not inspect until 4:00pm, call Dennis with any questions.###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa Inspection cancelled from web by: Daniel Gamboa
|
Electrical Rough-In | 4/27/2005 | 4/27/2005 | 4/27/2005 | P | PASS |
Bob Reichert
|
|
|
|
Electrical Rough-In | 4/27/2005 | 4/27/2005 | 4/27/2005 | P | PASS |
Bob Reichert
|
|
|
clg cover ok except where missing light
|
Final | 4/27/2005 | 4/27/2005 | 4/27/2005 | P | CANC |
Bob Reichert
|
|
|
This is for ceiling final call Dennis with any questions. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa see updated request 4/27/2005 4:26:06 PM
|
Electrical Rough-In | 4/22/2005 | 4/22/2005 | 4/22/2005 | P | NR |
Bob Reichert
|
|
|
ceiling inspection please///james; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ceilings not ready, borders ok except where j-box . 4/22/2005 4:22:41 PM
|
Electrical Rough-In | 4/14/2005 | 4/15/2005 | 4/15/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 4/14/2005 at 2:15:07 PM. ric bathroom walls only ok 4/15/2005 8:51:39 AM
|
Electrical Rough-In | 4/7/2005 | 4/8/2005 | 4/8/2005 | P | PASS |
Bob Reichert
|
|
|
james; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ric walls only ok 4/8/2005 1:33:28 PM
|
Conference | 4/6/2005 | 4/6/2005 | 4/6/2005 | P | DONE |
Bob Reichert
|
|
|
james; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles review light and sw at bottle stor area, and mc cable in patient care area for switches. Also fixture whips. Also told contr to use hospital grade mc cable to floor recpts. 4/6/2005 1:51:20 PM
|
Electrical Rough-In | 3/28/2005 | 3/29/2005 | 3/29/2005 | A | CANC |
Bob Reichert
|
|
|
dennis ###-#### called in wrong job for inspection 3/29/2005 10:14:49 AM
|
Electrical Rough-In | 3/22/2005 | 3/23/2005 | 3/23/2005 | A | FAIL |
Pat Lass
|
|
|
dennis Note: partial; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
517.13 no PVC to dental chairs 3/23/2005 11:57:26 AM
|
Electrical Rough-In | 3/23/2005 | 3/23/2005 | 3/23/2005 | P | PASS |
Bob Reichert
|
|
|
ok to pour slab only
|
Conference | 3/18/2005 | 3/18/2005 | 3/18/2005 | P | DONE |
Bob Reichert
|
|
|
dennis--call 1st before insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie met with elect about in-floor recpts, and grounding mc cable, plan checking,and quick job schedule 3/18/2005 4:31:28 PM
|