Final | 6/29/2005 | 6/29/2005 | 6/29/2005 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Moore corrections made, ok to final
|
Final | 6/28/2005 | 6/29/2005 | 6/29/2005 | A | FAIL |
Bob Reichert
|
|
|
dan; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, left message, left corr notice, 210.8(A)(7) utility sink shall have gfci protection within 6' of recpt, 404.9(A) switch shall have faceplate seat against finished surface, 422.31(B) dishwasher shall have lockout provisions
|
Electrical Rough-In | 3/24/2005 | 3/24/2005 | 3/24/2005 | P | PASS |
Bob Reichert
|
|
|
Brian; Phone #: ###-#### Internet Inspection Request from: Jan Rice corrections made ric ok 3/24/2005 1:56:16 PM
|
Rough-In Permanent Service | 3/23/2005 | 3/23/2005 | 3/23/2005 | P | PART |
Bob Reichert
|
|
|
brian-- ###-#### called contr, left corr notice, 334.80,adjust ampacity over panel,210.52 (H) entry shall have rcpt, 210.52(A)(2) dining room and loft shall have rcpt for 2' wall space p/s u/g n ok 3/23/2005 3:26:26 PM
|