Final | 6/28/2005 | 6/28/2005 | 6/28/2005 | P | PASS |
Bob Reichert
|
|
|
Please call Rob our j-ma n if this fails.; Phone #: ###-#### Internet Inspection Request from: KATHY WEIL corrections made, ok to final
|
Final | 6/21/2005 | 6/22/2005 | 6/22/2005 | A | FAIL |
Bob Reichert
|
|
|
Sorry about the permit number confusion!Please give Rob a call if this fails @###-####. Thank you!; Phone #: ###-#### Internet Inspection Request from: KATHY WEIL 408.4 panel schedule shall be done, 352.30(A) rnc shall be strapped within 3' of box, 314.21 drywall shall be repaired at faceplates
|
Electrical Rough-In | 3/29/2005 | 3/30/2005 | 3/30/2005 | P | PASS |
Bob Reichert
|
|
|
###-#### rob called contr about 1 1/4" ric ok, left message 3/30/2005 2:34:45 PM
|
Permanent Service | 3/30/2005 | 3/30/2005 | 3/30/2005 | P | PASS |
Bob Reichert
|
|
|
p/s u/g n ok
|