Final | 7/18/2005 | 7/19/2005 | 7/19/2005 | A | PASS |
Bob Reichert
|
|
|
call for access information///earl ; Phone #: ###-#### Internet Inspection Request from: Barbara Moore told elect, left survey 422.16(B) waste disposal cord shall be suitable for use. ok to final
|
Permanent Service | 6/22/2005 | 6/23/2005 | 6/23/2005 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 6/22/2005 at 7:41:39 PM. corrections made, p/s u/g n ok
|
Permanent Service | 6/22/2005 | 6/22/2005 | 6/22/2005 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 6/22/2005 at 6:43:05 AM. Contact: ###-####. only put bushings in inside panel, 312.5 and 352.30(A) not done, called left message, left corr notice, talked to elect, he will recall
|
Permanent Service | 6/18/2005 | 6/20/2005 | 6/20/2005 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 6/18/2005 at 7:19:01 PM. Contact: ###-####. called, left message, left corr notice, 300.4(F) & 344.46 Bushings shall be provided to protect wire from abrasion, 312.5 gec shall be protected from abrasion, 352.30 rnc shall be strapped within 3' of panel
|
Electrical Rough-In | 4/26/2005 | 4/27/2005 | 4/27/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 4/26/2005 at 6:56:42 PM. Contact: ###-####. corrections made, ric ok 4/27/2005 9:24:27 AM
|
Electrical Rough-In | 4/25/2005 | 4/25/2005 | 4/25/2005 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 4/25/2005 at 11:09:35 AM. Contact: ###-####. called contr, left corr notice, some items not done from 1st notice, some changes made, 314.3 box shall not use metal raceway unless listed, 314.20 box shall be flush with combustible material, 314.17(C) nm cable shall be stapled within 8" of box 4/25/2005 2:04:21 PM
|
Electrical Rough-In | 4/11/2005 | 4/11/2005 | 4/11/2005 | P | FAIL |
Bob Reichert
|
|
|
david; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, left corr notice, 300.4(D) 1 1/4" shall be maintained from edge if framing members,250.148(B) ground connections in box shall be continuous, 210.52(B)(2) hood shall not be on small appliance ckt, 110.12(A) un-used openings shall be closed in range box, 210.52(A)(1) &(2) 6' receptacle spacing shall be maintained, 310.15(B)(6) feeders too small for 200A panel 4/11/2005 1:35:29 PM
|