Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberELE05-01098
StatusFinaled
Name DAVID MCCLELLAN CONTRACTING
Site Address 5918 W ELMER LN
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/18/20057/19/20057/19/2005APASS
DetailsBob Reichert
call for access information///earl ; Phone #: ###-#### Internet Inspection Request from: Barbara Moore told elect, left survey 422.16(B) waste disposal cord shall be suitable for use. ok to final
Permanent Service6/22/20056/23/20056/23/2005PPASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 6/22/2005 at 7:41:39 PM. corrections made, p/s u/g n ok
Permanent Service6/22/20056/22/20056/22/2005PFAIL
DetailsBob Reichert
Scheduled by a contractor via Hello! on 6/22/2005 at 6:43:05 AM. Contact: ###-####. only put bushings in inside panel, 312.5 and 352.30(A) not done, called left message, left corr notice, talked to elect, he will recall
Permanent Service6/18/20056/20/20056/20/2005AFAIL
DetailsBob Reichert
Scheduled by a contractor via Hello! on 6/18/2005 at 7:19:01 PM. Contact: ###-####. called, left message, left corr notice, 300.4(F) & 344.46 Bushings shall be provided to protect wire from abrasion, 312.5 gec shall be protected from abrasion, 352.30 rnc shall be strapped within 3' of panel
Electrical Rough-In4/26/20054/27/20054/27/2005APASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 4/26/2005 at 6:56:42 PM. Contact: ###-####. corrections made, ric ok 4/27/2005 9:24:27 AM
Electrical Rough-In4/25/20054/25/20054/25/2005PFAIL
DetailsBob Reichert
Scheduled by a contractor via Hello! on 4/25/2005 at 11:09:35 AM. Contact: ###-####. called contr, left corr notice, some items not done from 1st notice, some changes made, 314.3 box shall not use metal raceway unless listed, 314.20 box shall be flush with combustible material, 314.17(C) nm cable shall be stapled within 8" of box 4/25/2005 2:04:21 PM
Electrical Rough-In4/11/20054/11/20054/11/2005PFAIL
DetailsBob Reichert
david; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, left corr notice, 300.4(D) 1 1/4" shall be maintained from edge if framing members,250.148(B) ground connections in box shall be continuous, 210.52(B)(2) hood shall not be on small appliance ckt, 110.12(A) un-used openings shall be closed in range box, 210.52(A)(1) &(2) 6' receptacle spacing shall be maintained, 310.15(B)(6) feeders too small for 200A panel 4/11/2005 1:35:29 PM