Final | 5/10/2005 | 5/10/2005 | 5/11/2005 | P | PASS |
Bob Reichert
|
|
|
dean ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok to final
|
Rough-In Permanent Service | 4/6/2005 | 4/6/2005 | 4/6/2005 | P | PASS |
Jack Frank
|
|
|
dino; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles r/i ok p/s u/g new ok 4/6/2005 12:16:47 PM
|
Electrical Rough-In | 4/4/2005 | 4/5/2005 | 4/5/2005 | A | FAIL |
Bob Reichert
|
|
|
###-#### - dino called contr, left corr notice,110.12(A) unused openings in panel shall be closed,110.12(C) boxes shall not be broken, 314.17(C) cable clamp shall be provided in pan boxes 4/5/2005 10:23:34 AM
|