Final | 5/10/2005 | 5/10/2005 | 5/11/2005 | P | PASS |
Bob Reichert
|
|
|
dean ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok to final
|
Rough-In Permanent Service | 4/6/2005 | 4/6/2005 | 4/6/2005 | P | PASS |
Jack Frank
|
|
|
dino; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles r/i ok p/s u/g new ok 4/6/2005 12:17:03 PM
|
Electrical Rough-In | 4/4/2005 | 4/5/2005 | 4/5/2005 | A | FAIL |
Bob Reichert
|
|
|
###-#### - dino called contr, left corr notice, 300.4(D) cable shall be 1 1/4" from edge of framing member, 110.12(C) broken boxes shall be replaced, 314.17(C) pan box shall have clamp 4/5/2005 10:30:32 AM
|