Final | 4/27/2005 | 4/28/2005 | 4/28/2005 | A | PASS |
Bob Reichert
|
|
|
final inspection on swimming pool Internet Inspection Request from: Andy Rose ok to final 4/28/2005 8:23:14 AM
|
Electrical Rough-In | 4/25/2005 | 4/26/2005 | 4/26/2005 | A | FAIL |
Bob Reichert
|
|
|
need potting inspection on pool Internet Inspection Request from: Andy Rose pool 1/2 full of water, called contr, left do not cover sticker 4/26/2005 9:29:02 AM
|
Electrical Rough-In | 4/26/2005 | 4/26/2005 | 4/26/2005 | P | PASS |
Bob Reichert
|
|
|
potting ispection on pool Internet Inspection Request from: Andy Rose potting ok 4/26/2005 2:26:17 PM
|
Electrical Rough-In | 4/21/2005 | 4/21/2005 | 4/21/2005 | A | PASS |
Bob Reichert
|
|
|
ok to pour walk area
|
Final | 4/20/2005 | 4/21/2005 | 4/21/2005 | A | CANC |
Bob Reichert
|
|
|
need bonding inspection on grid for new swimming pool Internet Inspection Request from: Andy Rose see added insp for ri, not final 4/21/2005 8:20:58 AM
|
Electrical Rough-In | 4/14/2005 | 4/14/2005 | 4/14/2005 | A | PASS |
Bob Reichert
|
|
|
corrections made, r/i pool only for bond ok. Need to see deck bond
|
Final | 4/13/2005 | 4/14/2005 | 4/14/2005 | A | CANC |
Bob Reichert
|
|
|
bonding inspection on swimming pool. ; Phone #: ###-#### Internet Inspection Request from: Andy Rose see next for r/i 4/14/2005 7:47:31 AM
|
Electrical Rough-In | 4/12/2005 | 4/13/2005 | 4/13/2005 | A | FAIL |
Bob Reichert
|
|
|
bonding inspection for new swimming pool Internet Inspection Request from: Andy Rose called, left message, left corr notice. 110.14 lugs shall be properly installed(by light), 680.26(C) provisions shall be made for equipotential bonding grid 4/13/2005 9:22:34 AM
|