Final | 6/15/2005 | 6/15/2005 | 6/15/2005 | P | PASS |
Bob Reichert
|
|
|
Steve; Phone #: ###-#### Internet Inspection Request from: Corrie Hall ok to final
|
Electrical Rough-In | 4/5/2005 | 4/6/2005 | 4/6/2005 | A | PASS |
Bob Reichert
|
|
|
steve; Phone #: ###-#### Internet Inspection Request from: Barbara Moore corrections made, ric ok 4/6/2005 7:35:22 AM
|
Permanent Service | 4/5/2005 | 4/5/2005 | 4/5/2005 | P | PASS |
Bob Reichert
|
|
|
p/s u/g n ok
|
Rough-In Permanent Service | 4/5/2005 | 4/5/2005 | 4/5/2005 | P | FAIL |
Bob Reichert
|
|
|
steve ###-#### called contr, left corr notice, 300.4(B) nm cable at heater shall have listed bushing or grommet, 334.80 ampacity of cable over panel shall be adjusted if foamed, 300.4(D) cable shall be 1 1/4" from edge of framing member, 210.52(A)(2) 2' wall space into kitchen shall have recpt, 314.27(A) box shall be provided for luminaire out back, BCC job id sticker shall be posted , p/s u/g n ok,see next insp. 4/5/2005 1:22:59 PM
|