Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberELE05-01136
StatusFinaled
Name POWERBOUND ELECTRIC INC
Site Address 9061 W DALTON PL
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/15/20056/15/20056/15/2005PPASS
DetailsBob Reichert
Steve; Phone #: ###-#### Internet Inspection Request from: Corrie Hall ok to final
Electrical Rough-In4/5/20054/6/20054/6/2005APASS
DetailsBob Reichert
steve; Phone #: ###-#### Internet Inspection Request from: Barbara Moore corrections made, ric ok 4/6/2005 7:35:22 AM
Permanent Service4/5/20054/5/20054/5/2005PPASS
DetailsBob Reichert
p/s u/g n ok
Rough-In Permanent Service4/5/20054/5/20054/5/2005PFAIL
DetailsBob Reichert
steve ###-#### called contr, left corr notice, 300.4(B) nm cable at heater shall have listed bushing or grommet, 334.80 ampacity of cable over panel shall be adjusted if foamed, 300.4(D) cable shall be 1 1/4" from edge of framing member, 210.52(A)(2) 2' wall space into kitchen shall have recpt, 314.27(A) box shall be provided for luminaire out back, BCC job id sticker shall be posted , p/s u/g n ok,see next insp. 4/5/2005 1:22:59 PM