Final | 8/3/2005 | 8/3/2005 | 8/3/2005 | P | PASS |
William E Thomas
|
|
|
larry; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
survey note- need additional recep by cooktop, smaller cooktop than on the plans have been used.
|
Electrical Rough-In | 4/7/2005 | 4/8/2005 | 4/8/2005 | A | PASS |
Pat Lass
|
|
|
larry; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
Permanent Service | 4/8/2005 | 4/8/2005 | 4/8/2005 | A | PASS |
Pat Lass
|
|
|
P/S U/G N Ok
|
Electrical Rough-In | 4/7/2005 | 4/7/2005 | 4/7/2005 | P | FAIL |
Bob Reichert
|
|
|
###-#### - larry called contr, left corr notice, 300.4(A)(1)&(D) nailplates and 1 1/4" shall be done as code states,BCC all make-up shall be done and boxes installed, 250.64(D) grounding electrode conductor tap shall be made outside of enclosure, 110.14(D) grounds shall be spliced with devices identified for the purpose, 314.16 boxes shall not exceed fill as calculated, 210.52 recpts shall be installed by fireplace if cabinets or cupboards in wall 4/7/2005 4:59:28 PM
|