Permit NumberELE05-01157
StatusFinaled
Name ELKSTONE ELECTRIC
Site Address 4455 N SETTLERS RIDGE PL
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/3/20058/3/20058/3/2005PPASS
DetailsWilliam E Thomas
larry; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa

survey note- need additional recep by cooktop, smaller cooktop than on the plans have been used.









Electrical Rough-In4/7/20054/8/20054/8/2005APASS
DetailsPat Lass
larry; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
Permanent Service4/8/20054/8/20054/8/2005APASS
DetailsPat Lass
P/S U/G N Ok
Electrical Rough-In4/7/20054/7/20054/7/2005PFAIL
DetailsBob Reichert
###-#### - larry called contr, left corr notice, 300.4(A)(1)&(D) nailplates and 1 1/4" shall be done as code states,BCC all make-up shall be done and boxes installed, 250.64(D) grounding electrode conductor tap shall be made outside of enclosure, 110.14(D) grounds shall be spliced with devices identified for the purpose, 314.16 boxes shall not exceed fill as calculated, 210.52 recpts shall be installed by fireplace if cabinets or cupboards in wall 4/7/2005 4:59:28 PM