Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberELE05-01204
StatusFinaled
Name MICHAEL J PENDER
Site Address 4100 W NORMANDIE DR
Project Name 
Customer Number 
ePlanReview 
Description
per customer michael pender need to add 5 more rooms to permit/9/27/05/mls
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/11/20075/15/20075/15/2007APASS
DetailsBob Reichert
mike ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corrections made ok to final
Final3/19/20073/20/20073/20/2007AFAIL
DetailsBob Reichert
Mike; Phone #: ###-#### Internet Inspection Request from: Stacie Backus met owner, left corr notice, nec 210.8(A) (6) & (2) & (3) kitchen and garage and outside receptacles shall be gfci protected, 408.4 circuit directory shall be clear, concise, and complete for each circuit, 422.31(B) water heater and furnace shall have disconnects, 110.3(B) equipment shall be installed per listing and labelling- no open grounds or reverse polarity, 210.12 arc fault protection shall be provided for bedroom circuit, 406.8(B) weatherproof in-use cover shall be provided outdoors
Electrical Rough-In11/13/200611/14/200611/14/2006APASS
DetailsBob Reichert
Mike, before 9:00 a.m. please; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to cover u/g to garage
Electrical Rough-In10/27/200610/30/200610/30/2006APASS
DetailsBob Reichert
michale; Phone #: ###-#### Note: if possible between 8:00 - 9:00 Internet Inspection Request from: Cathy Chiles met owner, told and gave list to put in ko seals, strap nm cable over panel, isolate gnd in panel, provide 4 wire recpt for dryer, nail plates 3 plcs, gave ok to cover, check panel at final
Electrical Rough-In10/19/200610/20/200610/20/2006ACANC
DetailsBob Reichert
mike Note: Please inspect 8:00 if possible; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles see p/s, wrong type inspection request
Permanent Service10/20/200610/20/200610/20/2006APASS
DetailsBob Reichert
mike Note: Please inspect 8:00 if possible; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s, o/h, rec, ok
Permanent Service8/11/20068/14/20068/14/2006ACANC
DetailsJack Frank
michael -call 1st before insp ###-#### cell
owner called and canceled
Conference4/21/20064/25/20064/25/2006ADONE
DetailsJack Frank
mike; Phone #: ###-#### Note: if possible at 8:00 going to work at 9: am Internet Inspection Request from: Cathy Chiles
C O W owner needs to read his book had WH tapped to dryer circuit with #12, needs washer circuit, bathrm circuit , box filll romex stapled on edge, needs to staple within 8" of boxes, needs to complete all wiring
ELE-Request for Extension10/27/200510/27/200510/28/2005PPASS
DetailsJim Schmer
###-#### - mike Note: Note finished yet should be in 60 days Extend only this one time, no more extensions - JMS
Conference5/5/20055/6/20055/6/2005ADONE
DetailsJack Frank
please call when know what time going out///mike; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
Electrical Rough-In5/6/20055/6/20055/6/2005APART
DetailsJack Frank
garage ok only needs boxes flush with siding, 314.20 outside light and recept called
Electrical Rough-In5/6/20055/6/20055/6/2005PPART
DetailsJack Frank
mike; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa din rm ok 5/6/2005 9:16:33 AM
Conference4/29/20055/2/20055/2/2005ADONE
DetailsJack Frank
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok 5/2/2005 8:49:29 AM
Electrical Rough-In5/2/20055/2/20055/2/2005APART
DetailsJack Frank
r/i ok for bedrm and 2 bath rms only owner is still messed up in other areas of house
Electrical Rough-In4/25/20054/25/20054/25/2005PFAIL
DetailsJack Frank
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Moore--call 1st before insp --after 12:30 not there ,,,, 2nd cor. posted
314.16 box fill , 210.52(B) remove DW from kit circuit, provide required circuit for DW, 334.30 staple romex where required,334.24 shall not bend romex less than 5 times diameter, uncover all wiring covered before inspection, shall wire smoke detectors as building code states shall be interlocked called J Storey, note told owner again he needs book on basic wiring and this is only a partial correction . correction notice posted for work done without permit or inspection this is prior work no violations to be retained p/s and sub panel added in garage also needs to update permit to match # of rooms work was done in 4/25/2005 3:36:04 PM
Electrical Rough-In4/15/20054/15/20054/15/2005AFAIL
DetailsJack Frank
cor.posted met owner 210.52(A) outlet spacing, bedrm and dinning, 314.29 shall not bury boxes 410.8 closet light, 210.52(D) outlet adjacent to sink, 110.14 splices and terminals all messed up 300.14 6" free length, BCC covered before inspection and no violations retained gas range wiring, COW
Final4/14/20054/15/20054/15/2005ACANC
DetailsJack Frank
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Note: after 9:00 am please no final r/i 4/15/2005 10:15:41 AM