Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE05-01251
StatusFinaled
Name ALL AMERICAN ELECTRIC
Site Address 2240 S COLE RD
Project Name 
Customer Number05-071
ePlanReview 
Description
installing lights, switches, outlets, 16 power outlets, 3 GFI outlets, 9 data drops, 200 amp service, fire alarm per initial cert of value $11,050//LEM///Final cert of value $11,050///5/26/05 BAS
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/23/20055/24/20055/24/2005APASS
DetailsJack Frank
Scheduled by a contractor via Hello! on 5/23/2005 at 10:23:53 PM. Contact: ###-####. ok card signed
Electrical Rough-In4/29/20054/29/20054/29/2005APASS
DetailsJack Frank
ceiling ok
Permanent Service4/28/20054/29/20054/29/2005APASS
DetailsJack Frank
Someone should be there but if not call ###-#### for the door code; Phone #: ###-#### Internet Inspection Request from: DJ Carman p/s u/g new meter ok 4/29/2005 9:18:41 AM
Temporary Service4/28/20054/29/20054/28/2005ACANC
DetailsJack Frank
Someone should be there but if not call ###-#### for the door code; Phone #: ###-#### Internet Inspection Request from: DJ Carman Inspection cancelled from web by: DJ Carman Inspection cancelled from web by: DJ Carman
Electrical Rough-In4/17/20054/18/20054/18/2005APASS
DetailsBob Reichert
Call for the door code. This is for a wall rough in inspection; Phone #: ###-#### Internet Inspection Request from: DJ Carman called contr, left survey, 330.30 cable shall be secured within 12" of box, 330.17 cable shall be protected in accordance with 300.4(D) 1 1/4" from edge of framing member. ric walls only 4/18/2005 9:40:34 AM
Electrical Rough-In4/14/20054/15/20054/15/2005ANH
DetailsPat Lass
dj; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
could not locate job called left message 4/15/2005 11:28:03 AM