Temporary Service | 4/25/2005 | 4/25/2005 | 4/25/2005 | P | PASS |
Pat Lass
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
T/S O/H Ok 4/25/2005 3:44:01 PM
|
Temporary Service | 4/15/2005 | 4/18/2005 | 4/18/2005 | A | FAIL |
Bob Reichert
|
|
|
mark ###-#### called contr, no answer, told builder, left corr notice, 225.22 emt conn shall be raintight listed, 314.17 gnd wire shall be protected from abrasion, 110.12(A) unused openings shall be closed 4/18/2005 8:40:48 AM
|