Final | 9/26/2005 | 9/27/2005 | 9/27/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/26/2005 at 12:39:45 PM. Contact: ###-####. corrections made, ok to final
|
Final | 8/18/2005 | 8/19/2005 | 8/19/2005 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 8/18/2005 at 12:14:25 PM. Contact: ###-####. told contr, left corr notice,605.3 wireways shall be free of projections that may damage conductor insulation(power, comm),605.4 partitions shall be connrcted with strain relief, 605.2(B) all nec articles apply and shall be adhered to(close openings,secure covers,provide plates for conduit fittings, comm. protection)
|