ELE-Aging Inspection | 6/29/2005 | 6/29/2005 | 6/29/2005 | | PASS |
Mike Kinnear
|
|
|
passed 4/26/05 315
|
Final | 6/29/2005 | 6/29/2005 | 6/29/2005 | P | PASS |
Mike Kinnear
|
|
|
temp ser. passed 4/26/05 315
|
Temporary Service | 4/25/2005 | 4/26/2005 | 4/26/2005 | A | PASS |
Jack Frank
|
|
|
no final, t/s o/h new ok 4/26/2005 8:23:24 AM
|
Temporary Service | 4/25/2005 | 4/25/2005 | 4/25/2005 | P | FAIL |
Jack Frank
|
|
|
jim-- ###-#### cor. posted inside of t/s called 240.24(A) t/s too high 6 ft 7" to highest breaker position, 110.3(B),550.33&11(D) shall provide 100 amp to job trailer as nameplate states, 550.32(A) service shall be within 30ft of trailer 4/25/2005 1:59:42 PM
|