Final | 7/7/2005 | 7/8/2005 | 7/8/2005 | A | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: KATHY WEIL ok final corrections made
|
Final | 6/29/2005 | 6/30/2005 | 6/30/2005 | A | FAIL |
Bob Reichert
|
|
|
Call Rob if this fails at ###-####; Phone #: ###-#### Internet Inspection Request from: KATHY WEIL called contr, left corr notice, 352.30(A) rnc shall be fastened within 3' of box,406.5,404.9 faceplates shall cover openings and seat against mounting surface, 110.26(A)(2) panel shall have 30" wide work space,210.8(A)(3) outdoor recpts shall have gfci, 422.16(A) disposal cord connector shall be tight,210.70(A)(2) light shall be in stairway, 408.4 circuit directory shall be specific
|
Electrical Rough-In | 5/9/2005 | 5/9/2005 | 5/9/2005 | P | PASS |
Mike Kinnear
|
|
|
rob; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok cover underground conduit
|
Permanent Service | 5/9/2005 | 5/9/2005 | 5/9/2005 | P | PASS |
Mike Kinnear
|
|
|
rob; Phone #: ###-#### Internet Inspection Request from: Barbara Moore p/s u/g n ok
|
Electrical Rough-In | 5/5/2005 | 5/6/2005 | 5/6/2005 | A | PASS |
Pat Lass
|
|
|
cathy; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
R/I Ok 5/6/2005 9:04:36 AM
|
Electrical Rough-In | 5/4/2005 | 5/5/2005 | 5/5/2005 | A | NR |
Mike Kinnear
|
|
|
###-#### cathy conf with contractor
|