Final | 7/7/2005 | 7/8/2005 | 7/8/2005 | A | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: KATHY WEIL ok final correction made
|
Final | 6/29/2005 | 6/30/2005 | 6/30/2005 | A | FAIL |
Bob Reichert
|
|
|
Call Rob if this fails at ###-####; Phone #: ###-#### Internet Inspection Request from: KATHY WEIL called contr, left corr notice, 406.5,404.9 faceplates shall cover openings and seat against mounting surface,408.4 circuit directory shall be specific, 110.26(A)(2) panel shall have 30" wide work space, 422.16(B)(1)(2) disposal cord shall be max 3' long,210.8(A)(3) outdoor recpts shall be gfci, 314.21 sheetrock shall be repaired in util room for light, 210.70(A)(2)(a) light shall be in stairway
|
Electrical Rough-In | 5/9/2005 | 5/9/2005 | 5/9/2005 | P | PASS |
Mike Kinnear
|
|
|
kathy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok cover underground conduit
|
Permanent Service | 5/9/2005 | 5/9/2005 | 5/9/2005 | P | PASS |
Mike Kinnear
|
|
|
kathy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore p/s u/g n ok
|
Electrical Rough-In | 5/5/2005 | 5/6/2005 | 5/6/2005 | A | PASS |
Pat Lass
|
|
|
cathy; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
R/I Ok
service not ready 5/6/2005 9:05:02 AM
|
Electrical Rough-In | 5/4/2005 | 5/5/2005 | 5/5/2005 | A | NR |
Mike Kinnear
|
|
|
###-#### cathy conf with contractor
|