Final | 9/14/2005 | 9/15/2005 | 9/15/2005 | A | PASS |
Bob Reichert
|
|
|
dan; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
|
Rough-In Permanent Service | 5/24/2005 | 5/24/2005 | 5/24/2005 | P | PASS |
Bob Reichert
|
|
|
dan ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie corrections made, ric ok, p/s u/g n ok
|
Electrical Rough-In | 5/23/2005 | 5/23/2005 | 5/23/2005 | P | FAIL |
Bob Reichert
|
|
|
###-#### - dan - Note: cover 314.17(A) openings shall be closed where conductors enter(can lights), 314.20, in walls of combustible material, boxes shall be flush with finished surface(so garage lite), 250.148(C) metal boxes shall be grounded, BC
|
Permanent Service | 5/23/2005 | 5/23/2005 | 5/23/2005 | P | FAIL |
Bob Reichert
|
|
|
###-#### - dan 312.5 conductors entering enclosures shall be protected from abrasion (gec into panel)
|