DOC - Permit Finaled | | | 3/30/2015 | | DONE |
|
|
|
|
DOC - Permit Expired | 9/23/2008 | 9/23/2008 | 9/23/2008 | A | PASS |
Jack Frank
|
|
|
|
Electrical Rough-In | 6/15/2005 | 6/15/2005 | 6/15/2005 | P | PASS |
Bob Reichert
|
|
|
###-#### - seid told bldr to have owner change gnd strap in panel and to put in ko seal in panel. corrections made, ric ok, called contr to re -wire meter for service and to call for p/s.
|
Electrical Rough-In | 6/10/2005 | 6/13/2005 | 6/13/2005 | A | FAIL |
Bob Reichert
|
|
|
dale; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa 314.20 boxes shall be flush with finished surface, 210.12(B) bedrooms shall be supplied with afci, BCC all make up shall be done(grounds tied together in boxes)
|
Electrical Rough-In | 6/3/2005 | 6/6/2005 | 6/6/2005 | A | FAIL |
Bob Reichert
|
|
|
###-#### called, no answer, left corr notice, 210.52(D) bath recpts shall be within 3' of basin, 210.52(A)(2) recpts shall be installed in wall space over 2'-0", 300.4(A)(1) bored hole shall be 1 1/4" from edge of framing member,300.4(B)(2) nm cable shall be 1 1/4" from edge of framing member, 314.20 boxes shall be flush with finished surface,314.15(A) fittings shall be listed for use in wet locations,210.70(A)(2) switch for stairs shall be provided at each level. BCC all make-up shall be done, job id sticker shall be posted, approved set of plans shall be on job
|