Final | 7/13/2005 | 7/13/2005 | 7/13/2005 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 7/13/2005 at 7:23:48 AM. Contact: ###-####. ok to final
|
Final | 7/11/2005 | 7/12/2005 | 7/12/2005 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 7/11/2005 at 12:55:40 PM. told contr, left corr notice,408.4 circuit directory shall be specific with detail,352.30 rnc shall be strapped within 3' of panel, recpt east garage, check wiring, 314.15 box shall be listed for wet location, fee due
|
Rough-In Permanent Service | 6/6/2005 | 6/7/2005 | 6/7/2005 | A | PASS |
Bob Reichert
|
|
|
clyde ###-#### talked to elect and put on np, ric ok, p/s u/g n ok
|