Final | 2/6/2007 | 2/7/2007 | 2/7/2007 | A | PASS |
Bob Reichert
|
|
|
JARED ; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok to final, will sign card after elev inspection, pits ok
|
Final | 1/29/2007 | 1/30/2007 | 1/30/2007 | A | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 1/29/2007 at 4:32:02 PM. Contact: ###-####. pool light potting ok, a/c listed ok, pump gone ok
|
Final | 1/22/2007 | 1/23/2007 | 1/23/2007 | P | PART |
Jack Frank
|
|
|
jerad - final on 1st and 2nd floor hall ways; Phone #: ###-#### Internet Inspection Request from: Victoria Beall t/o ok card signed all that ie left is new listed compressor for sprinkler system, pool rooftop&equip rm, lobby&kit rooftop
|
Final | 1/15/2007 | 1/16/2007 | 1/16/2007 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 1/15/2007 at 3:19:03 PM. Contact: ###-####. t/o anop 3rd and 4th floor corridors and r/i front desk area
|
Electrical Rough-In | 1/9/2007 | 1/10/2007 | 1/10/2007 | A | PASS |
Mike Kinnear
|
|
|
jared - pool bonding ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok bonding latters
|
Final | 1/3/2007 | 1/4/2007 | 1/4/2007 | A | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 1/3/2007 at 11:14:38 AM. Contact: ###-####. rooms anop ok to final and clgs anop ok to cover
|
Final | 12/14/2006 | 12/15/2006 | 12/15/2006 | A | PART |
Jack Frank
|
|
|
jared - the north half - 1st floor ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok anop
|
Final | 12/11/2006 | 12/12/2006 | 12/12/2006 | A | PART |
Bob Reichert
|
|
|
jarod - half the 1st floor guest rooms ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith 1st fl clgs ok to cover anop, 1st floor rooms anop ok to final
|
Final | 12/4/2006 | 12/5/2006 | 12/5/2006 | A | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 12/4/2006 at 12:03:01 PM. Contact: ###-####. 2nd fl rooms anop ok to final
|
Final | 11/21/2006 | 11/22/2006 | 11/22/2006 | A | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 11/21/2006 at 1:29:29 PM. 3rd fl anop ok to final
|
Final | 11/14/2006 | 11/15/2006 | 11/15/2006 | A | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 11/14/2006 at 2:37:49 PM. Contact: ###-####. roof, attic, so 1/2 3rd floor anop ok to final
|
Final | 11/10/2006 | 11/13/2006 | 11/13/2006 | A | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 11/10/2006 at 1:55:24 PM. Contact: ###-####. west 4th floor rooms anop ok to final
|
Final | 11/7/2006 | 11/8/2006 | 11/9/2006 | A | PART |
Bob Reichert
|
|
|
jared - half of the 4th floor ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith rooms only anop ok to final, south part, no halls
|
Electrical Rough-In | 10/13/2006 | 10/16/2006 | 10/16/2006 | A | PART |
Jack Frank
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok
|
Electrical Rough-In | 10/12/2006 | 10/13/2006 | 10/13/2006 | P | PART |
Jack Frank
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles front canopy lighting anop ok
|
Electrical Rough-In | 10/12/2006 | 10/13/2006 | 10/12/2006 | A | CANC |
Jack Frank
|
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Patricia Smith Inspection cancelled from web by: Cathy Chiles
|
Electrical Rough-In | 10/5/2006 | 10/5/2006 | 10/5/2006 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/5/2006 at 7:03:52 AM. Contact: ###-####. ceiling in billiards rm
|
Electrical Rough-In | 9/13/2006 | 9/13/2006 | 9/13/2006 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 9/13/2006 at 7:41:41 AM. Contact: ###-####. u/g and lobby hard ceiling anop
|
Electrical Rough-In | 9/7/2006 | 9/8/2006 | 9/8/2006 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 9/7/2006 at 4:01:04 PM. Contact: ###-####. ceilings pool area and pool equip rm anop
|
Rough-In Permanent Service | 8/29/2006 | 8/29/2006 | 8/29/2006 | P | PASS |
Jack Frank
|
|
|
jerad; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley r/i ok anop p/s u/g new ok
|
Electrical Rough-In | 8/21/2006 | 8/21/2006 | 8/21/2006 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 8/21/2006 at 7:06:54 AM. Contact: ###-####. ceiling ok corridor
|
Electrical Rough-In | 8/14/2006 | 8/15/2006 | 8/15/2006 | A | PART |
Jack Frank
|
|
|
jerod Note; exercise room 1st floor; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok anop
|
Electrical Rough-In | 8/10/2006 | 8/10/2006 | 8/10/2006 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 8/10/2006 at 8:00:39 AM. Contact: ###-####. 3rd floor hard lids anop
|
Electrical Rough-In | 8/4/2006 | 8/4/2006 | 8/4/2006 | P | PART |
Jack Frank
|
|
|
pool spa E grid ok walls ok pool rm
|
Electrical Rough-In | 8/3/2006 | 8/4/2006 | 8/4/2006 | A | PART |
Jack Frank
|
|
|
jared - pool ground & hard-lid ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley no pool E grid 4th floor ok anop
|
Electrical Rough-In | 7/28/2006 | 7/31/2006 | 7/31/2006 | A | PART |
Jack Frank
|
|
|
jared - 3rd fl hard lids; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok anop
|
Electrical Rough-In | 7/18/2006 | 7/19/2006 | 7/19/2006 | A | PASS |
Jim Schmer
|
|
|
jared - underground ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley so end of bld jms
|
Electrical Rough-In | 6/27/2006 | 6/28/2006 | 6/28/2006 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/27/2006 at 3:40:02 PM. Contact: ###-####. 1st floor anop
|
Electrical Rough-In | 6/14/2006 | 6/14/2006 | 6/14/2006 | P | PART |
Jack Frank
|
|
|
jerod Note: 1/2 4th floor - hard lid; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
Electrical Rough-In | 6/6/2006 | 6/7/2006 | 6/7/2006 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/6/2006 at 3:41:15 PM. Contact: ###-####. 2nd floor anop 4th floor anop
|
Electrical Rough-In | 5/24/2006 | 5/25/2006 | 5/25/2006 | A | PART |
Mike Kinnear
|
|
|
jerod; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok cover ri anop
|
Electrical Rough-In | 4/28/2006 | 5/1/2006 | 5/1/2006 | A | PART |
Jack Frank
|
|
|
jerod Note: 3rd floor east half; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles 3rd floor east wing anop
|
Electrical Rough-In | 4/25/2006 | 4/26/2006 | 4/26/2006 | A | PART |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Marsha Smylie 3rd and 4th floors anop
|
Electrical Rough-In | 4/24/2006 | 4/25/2006 | 4/25/2006 | A | PART |
Jack Frank
|
|
|
jerad; Phone #: ###-#### Note: not the entire bld - freak out 1/2 floor Internet Inspection Request from: Cathy Chiles ok panel rms 1,2,3,4 panel rm ceilings anop, 4th floor rm walls ceiling, corridors walls anop
|
Electrical Rough-In | 4/25/2006 | 4/25/2006 | 4/25/2006 | A | PART |
Jack Frank
|
|
|
jerad; Phone #: ###-#### Note: not the entire bld - freak out 1/2 floor Internet Inspection Request from: Cathy Chiles r/i 1/2 4th floor anop
|
ELE-Aging Inspection | 4/17/2006 | 4/17/2006 | 4/17/2006 | | NR |
Jack Frank
|
|
|
stooped at site wsuc
|
ELE-Aging Inspection | 2/13/2006 | 2/13/2006 | 2/14/2006 | | PART |
Jack Frank
|
|
|
wsuc
|
Conference | 12/12/2005 | 12/13/2005 | 12/13/2005 | P | DONE |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 12/12/2005 at 4:10:15 PM. Contact: ###-####.
|
Electrical Rough-In | 11/22/2005 | 11/22/2005 | 11/22/2005 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 11/22/2005 at 7:09:56 AM. Contact: ###-####. pool & spa bond ok no equipotential grid
|
Conference | 11/21/2005 | 11/21/2005 | 11/21/2005 | P | PART |
Jack Frank
|
|
|
con. on pool ok
|
ELE-Aging Inspection | 10/31/2005 | 10/31/2005 | 10/31/2005 | | PART |
Jack Frank
|
|
|
wsuc
|
Electrical Rough-In | 8/30/2005 | 8/30/2005 | 8/30/2005 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 8/30/2005 at 8:49:15 AM. Contact: ###-####. u/g anop
|
Conference | 8/9/2005 | 8/11/2005 | 8/11/2005 | A | DONE |
Jack Frank
|
|
|
meeting at 9 am per jim storey
|
Electrical Rough-In | 7/7/2005 | 7/7/2005 | 7/7/2005 | P | PASS |
Mike Kinnear
|
|
|
underground -jerad; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok cover underground duct bank
|
Electrical Rough-In | 6/29/2005 | 6/30/2005 | 6/30/2005 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/29/2005 at 4:38:29 PM. Contact: ###-####. u/g for feeders from gear to N W corner
|
Electrical Rough-In | 6/14/2005 | 6/15/2005 | 6/15/2005 | A | PART |
Jack Frank
|
|
|
underground u-fer//jared; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa partial duct bank and concrete encased electrode
|
Electrical Rough-In | 6/8/2005 | 6/9/2005 | 6/9/2005 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/8/2005 at 4:46:40 PM. Contact: ###-####. u/g for pole lights east and south
|