Final | 7/6/2005 | 7/7/2005 | 7/7/2005 | A | FAIL |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Terry Ayers voided permit called barb -- business can not have home owner permit.
|
Final | 7/5/2005 | 7/6/2005 | 7/6/2005 | A | FAIL |
Bob Reichert
|
|
|
New service was install and is open for inspection; Phone #: ###-#### Internet Inspection Request from: Terry Ayers told owner he had to strap service cnd, use correct straps, use water tight listed emt connectors, ground elect cond to tie to gnded cnd in panel, put bushings on gnd wire, change dryer and range to 4 wire sys
|
Final | 6/28/2005 | 6/28/2005 | 6/28/2005 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/28/2005 at 10:18:38 AM. Contact: ###-####. cor. posted met owner service shall meet current code , no violations to be retained needs clearence for o/h, grounding, main disconnect, proper overcurrent protection for branch circuit, open wiring in walls, protect all exposed cables WH, connectors for all cables
|
Permanent Service | 6/24/2005 | 6/27/2005 | 6/27/2005 | A | NH |
Bob Reichert
|
|
|