Final | 7/27/2005 | 7/28/2005 | 7/28/2005 | A | FAIL |
Jack Frank
|
|
|
Repaired mast, changed meterbase, & grounded. ; Phone #: ###-#### Internet Inspection Request from: Dana Moyer called cor. posted all violations not corrected, and W H needs #10 and 30 amp
|
Permanent Service | 6/27/2005 | 6/28/2005 | 6/28/2005 | A | FAIL |
Jack Frank
|
|
|
kyle; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa cor. posted called 110.26(F)(1) clearence for p/s, 250.24(B) install bond screw, 250.92(A)(3) install bond bushings both ends of nipple between meter and p/s, 240.51&310.16 protect conductors at proper amps and install type S fuses and adaptors evidence of overfusing is present, 250.52(A)(10 or 104(A)(1) grd or bond water system,, B C C no violations to be retained
|
Final | 6/27/2005 | 6/28/2005 | 6/28/2005 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/27/2005 at 3:35:08 PM. Contact: ###-####.
|