Final | 6/13/2007 | 6/13/2007 | 6/13/2007 | P | PASS |
Bob Reichert
|
|
|
Larry ; Phone #: ###-#### Internet Inspection Request from: Darla Downs told owner to chg a/c bkr and add wh disc, ok to final
|
Electrical Rough-In | 3/13/2007 | 3/14/2007 | 3/14/2007 | A | PASS |
Bob Reichert
|
|
|
Larry; Phone #: ###-#### Internet Inspection Request from: Stacie Backus corr made, ric ok
|
Electrical Rough-In | 3/12/2007 | 3/12/2007 | 3/12/2007 | P | FAIL |
William E Thomas
|
|
|
Larry ; Phone #: ###-#### Internet Inspection Request from: Stacie Backus 300.4A&D--1/14"protection, 314.16B--Box Fill, 300.14--free length of conductor, 314.17C--cables fastened within 8"
|