Rough-In Permanent Service | 7/7/2005 | 7/8/2005 | 7/8/2005 | A | CANC |
Jim Schmer
|
|
|
brandon ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
Rough-In Permanent Service | 7/6/2005 | 7/6/2005 | 7/6/2005 | P | FAIL |
Bob Reichert
|
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called left message, corr notice, 250.64(c) gec shall be installed in one continuous length without splice or joint, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, 210.52(A)(2) wall space over 2' shall have recpt, BCC job id shall be posted, approved set of plans shall be on job
|