Final | 11/8/2005 | 11/8/2005 | 11/8/2005 | P | PASS |
Pat Lass
|
|
|
justin; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
|
Final | 11/7/2005 | 11/7/2005 | 11/7/2005 | P | FAIL |
Bob Reichert
|
|
|
justin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, 210.52(C)(1) recpt shall be added by range, 210.52(A)(2) garage recpts shall be gfci, 422.31(B) dishwasher shall have lockout provided at breaker, 408.4 circuit 9 shall be explicit, 406.5 recpt faceplates shall seat against mounting surface,110.13(A) front recpt cover shall be secure and operate
|
Final | 10/12/2005 | 10/13/2005 | 10/13/2005 | A | NR |
Pat Lass
|
|
|
###-#### general was installing a new kitchen floor and had removed cabinets so I was unable to do a complete inspection at this time. I called the contractor about reschedualing and garage GFCIs and outside recep cover not fitting with the recep.
|
Rough-In Permanent Service | 7/7/2005 | 7/7/2005 | 7/7/2005 | P | PASS |
Jim Schmer
|
|
|
justin ###-#### p/s u/g new
|