Permit Information
Permit NumberELE05-02402
StatusFinaled
Name METCO ELECTRIC CO
Site Address 2809 W GAVIN ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/8/200511/8/200511/8/2005PPASS
DetailsPat Lass
justin; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
Final11/7/200511/7/200511/7/2005PFAIL
DetailsBob Reichert
justin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, 210.52(C)(1) recpt shall be added by range, 210.52(A)(2) garage recpts shall be gfci, 422.31(B) dishwasher shall have lockout provided at breaker, 408.4 circuit 9 shall be explicit, 406.5 recpt faceplates shall seat against mounting surface,110.13(A) front recpt cover shall be secure and operate
Final10/12/200510/13/200510/13/2005ANR
DetailsPat Lass
###-####
general was installing a new kitchen floor and had removed cabinets so I was unable to do a complete inspection at this time.
I called the contractor about reschedualing and garage GFCIs and outside recep cover not fitting with the recep.
Rough-In Permanent Service7/7/20057/7/20057/7/2005PPASS
DetailsJim Schmer
justin ###-#### p/s u/g new