Final | 11/4/2005 | 11/4/2005 | 11/4/2005 | P | PASS |
Bob Reichert
|
|
|
brian; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ok to final
|
Final | 11/3/2005 | 11/3/2005 | 11/3/2005 | P | FAIL |
Bob Reichert
|
|
|
brian; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, left corr notice, 210.8(A)(7) recpt in laundry shall be gfci, 410.8(D) closet lite shall be 6" from shelf, 110.3(B) garage 3-way switch shall operate correctly,680.73 access to jetted tub shall not be grouted in.
|
Rough-In Permanent Service | 7/27/2005 | 7/28/2005 | 7/28/2005 | A | PASS |
Bob Reichert
|
|
|
brian ###-#### ric ok p/s u/g n ok
|