Final | 8/18/2005 | 8/18/2005 | 8/18/2005 | P | PASS |
Mike Kinnear
|
|
|
Grounding inspection; Phone #: ###-#### Internet Inspection Request from: Celinda Winters ok final
|
Final | 8/11/2005 | 8/11/2005 | 8/11/2005 | P | NR |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters contractor corrected his part owner needs to correct his part of correction notice no final is to keep permit active, owner said he will have contractor make corrections told him he has one week to correct violations if ? call me 250.24(A)(1&5) GEC shall terminate at p/s , not sub panel and isolate grds and neutrals at sub panel, 110.3(B) use manufactures listed breakers only
|
Final | 8/8/2005 | 8/8/2005 | 8/8/2005 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters cor. posted for elect. contractor, and one for owner,300.21 for elect contractor panel not allowed in warm wall, owner no violations to be retained address service as service needs grds to p/s address sub panel as sub panel, use only manufactures breakers
|