Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE05-02806
StatusFinaled
Name ELCOR ELECTRIC
Site Address 247 N MILWAUKEE ST
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Alteration: Altering a clothing store into a jewlery store existing building remodel
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/3/200511/4/200511/4/2005APASS
DetailsMike Kinnear
Final Inspection. Thanks.; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen correction made ok final
Final11/3/200511/3/200511/3/2005PFAIL
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen still no panel schedules, covers off panels, said to finish that part of corrections before final.
Final11/2/200511/2/200511/2/2005PPART
DetailsBob Reichert
Late afternoon inspection if possible. Thanks.; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen left corr notice,250 bond hot and cold water pipe,210.8 add gfci within 25' of rooftop unit, 408.4 add panel schedules, 210.8 gfci by sink 400.8 lite shall not be cord connected
Permanent Service10/27/200510/27/200510/27/2005PPART
DetailsBob Reichert
Service Inspection; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen talked to contr, left corr notice, 110.3(B) 480V service shall be listed for service entrance, 376.23(A) and(B) wireway shall be as per 312.6, and 314.28(A)(2)
Electrical Rough-In10/26/200510/27/200510/27/2005APASS
DetailsBob Reichert
Phone #: ###-#### called cont, clg cover ok, add showroom recpts before final
Electrical Rough-In10/24/200510/24/200510/24/2005PFAIL
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen left corr notice, met contr, 300.11(A) independent support wires shall be secured at both ends.
Electrical Rough-In10/20/200510/20/200510/20/2005PCANC
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen Inspection cancelled from web by: Ryan Christensen
Electrical Rough-In10/19/200510/20/200510/20/2005ANR
DetailsBob Reichert
INSPECTION FOR THE CEILING COVER; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called contr, nr, will call ltr
Rough-In Permanent Service10/11/200510/11/200510/11/2005PCANC
DetailsBob Reichert
Thank you.; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen see ri
Electrical Rough-In10/11/200510/11/200510/11/2005PPASS
DetailsBob Reichert
Thank you.; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen baths ok to cover
Electrical Rough-In10/7/200510/7/200510/7/2005PFAIL
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen met with contractor, left correction notice, BCC no violations shall be retained, 358.30 Emt shall be fastened within 3' of box, 330.30(B) mc cable shall be strapped within 12" of box, 250.64(B) gec shall be secured in place,BCC no cover shall be done prior to inspection, 250.86 metal boxes shall be grounded
Rough-In Permanent Service9/28/20059/29/20059/29/2005APART
DetailsBob Reichert
Rough-In Inspection; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen ok to cover clg in diamond area east side where 4 fixtures are.
Electrical Rough-In9/22/20059/22/20059/22/2005PPASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen ok to cover walls only in repair area
Electrical Rough-In9/21/20059/21/20059/21/2005PPART
DetailsBob Reichert
south; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover soffit in diamond area only
Electrical Rough-In9/20/20059/20/20059/20/2005APART
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen walls only except repair area ok to cover
Electrical Rough-In9/18/20059/19/20059/19/2005PCANC
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen Inspection cancelled from web by: Ryan Christensen
Rough-In Permanent Service9/16/20059/16/20059/16/2005PFAIL
DetailsBob Reichert
Late afternoon if possible; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen talked with contr, left corr notice, NEC 358.30(A) emt shall be secureley fastened within 3' of box, 330.30 mc cable shall be secured within 12" of box, 300.4(D) & (E) mc cable shall be min 1 1/4" from edge of framing member and if in groove protected by minimum 1/16" steel plate. raceways shall not be in c of channel,BCC all make-up shall be done, mud rings attached. Electrician shall get classification of NEC Art. 500.5 for locations using natural gas and oxygen.
Electrical Rough-In8/24/20058/24/20058/24/2005PPASS
DetailsBob Reichert
ryan Note: late afternoon underground; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover u/g in slab only
Electrical Rough-In8/20/20058/22/20058/22/2005AFAIL
DetailsJack Frank
Inspection for under slab electrical. area needed is in main floor where the concrete has been removed and is ready to be replaced; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen
cor. posted called BCC u/g covered before inspection