Final | 11/3/2005 | 11/4/2005 | 11/4/2005 | A | PASS |
Mike Kinnear
|
|
|
Final Inspection. Thanks.; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen correction made ok final
|
Final | 11/3/2005 | 11/3/2005 | 11/3/2005 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen still no panel schedules, covers off panels, said to finish that part of corrections before final.
|
Final | 11/2/2005 | 11/2/2005 | 11/2/2005 | P | PART |
Bob Reichert
|
|
|
Late afternoon inspection if possible. Thanks.; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen left corr notice,250 bond hot and cold water pipe,210.8 add gfci within 25' of rooftop unit, 408.4 add panel schedules, 210.8 gfci by sink 400.8 lite shall not be cord connected
|
Permanent Service | 10/27/2005 | 10/27/2005 | 10/27/2005 | P | PART |
Bob Reichert
|
|
|
Service Inspection; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen talked to contr, left corr notice, 110.3(B) 480V service shall be listed for service entrance, 376.23(A) and(B) wireway shall be as per 312.6, and 314.28(A)(2)
|
Electrical Rough-In | 10/26/2005 | 10/27/2005 | 10/27/2005 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### called cont, clg cover ok, add showroom recpts before final
|
Electrical Rough-In | 10/24/2005 | 10/24/2005 | 10/24/2005 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen left corr notice, met contr, 300.11(A) independent support wires shall be secured at both ends.
|
Electrical Rough-In | 10/20/2005 | 10/20/2005 | 10/20/2005 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen Inspection cancelled from web by: Ryan Christensen
|
Electrical Rough-In | 10/19/2005 | 10/20/2005 | 10/20/2005 | A | NR |
Bob Reichert
|
|
|
INSPECTION FOR THE CEILING COVER; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called contr, nr, will call ltr
|
Rough-In Permanent Service | 10/11/2005 | 10/11/2005 | 10/11/2005 | P | CANC |
Bob Reichert
|
|
|
Thank you.; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen see ri
|
Electrical Rough-In | 10/11/2005 | 10/11/2005 | 10/11/2005 | P | PASS |
Bob Reichert
|
|
|
Thank you.; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen baths ok to cover
|
Electrical Rough-In | 10/7/2005 | 10/7/2005 | 10/7/2005 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen met with contractor, left correction notice, BCC no violations shall be retained, 358.30 Emt shall be fastened within 3' of box, 330.30(B) mc cable shall be strapped within 12" of box, 250.64(B) gec shall be secured in place,BCC no cover shall be done prior to inspection, 250.86 metal boxes shall be grounded
|
Rough-In Permanent Service | 9/28/2005 | 9/29/2005 | 9/29/2005 | A | PART |
Bob Reichert
|
|
|
Rough-In Inspection; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen ok to cover clg in diamond area east side where 4 fixtures are.
|
Electrical Rough-In | 9/22/2005 | 9/22/2005 | 9/22/2005 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen ok to cover walls only in repair area
|
Electrical Rough-In | 9/21/2005 | 9/21/2005 | 9/21/2005 | P | PART |
Bob Reichert
|
|
|
south; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover soffit in diamond area only
|
Electrical Rough-In | 9/20/2005 | 9/20/2005 | 9/20/2005 | A | PART |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen walls only except repair area ok to cover
|
Electrical Rough-In | 9/18/2005 | 9/19/2005 | 9/19/2005 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen Inspection cancelled from web by: Ryan Christensen
|
Rough-In Permanent Service | 9/16/2005 | 9/16/2005 | 9/16/2005 | P | FAIL |
Bob Reichert
|
|
|
Late afternoon if possible; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen talked with contr, left corr notice, NEC 358.30(A) emt shall be secureley fastened within 3' of box, 330.30 mc cable shall be secured within 12" of box, 300.4(D) & (E) mc cable shall be min 1 1/4" from edge of framing member and if in groove protected by minimum 1/16" steel plate. raceways shall not be in c of channel,BCC all make-up shall be done, mud rings attached. Electrician shall get classification of NEC Art. 500.5 for locations using natural gas and oxygen.
|
Electrical Rough-In | 8/24/2005 | 8/24/2005 | 8/24/2005 | P | PASS |
Bob Reichert
|
|
|
ryan Note: late afternoon underground; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover u/g in slab only
|
Electrical Rough-In | 8/20/2005 | 8/22/2005 | 8/22/2005 | A | FAIL |
Jack Frank
|
|
|
Inspection for under slab electrical. area needed is in main floor where the concrete has been removed and is ready to be replaced; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen cor. posted called BCC u/g covered before inspection
|