Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberELE05-02816
StatusFinaled
Name S & D ELECTRIC
Site Address 1212 N PIKE ST
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Addition: adding 2 bath,2 bedroom, and 1 office
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/4/20061/5/20061/5/2006PPASS
DetailsMike Kinnear
Please call one hour before if at all possible. Thanks.; Phone #: ###-#### Internet Inspection Request from: steven sewell ok final
Rough-In Permanent Service8/4/20058/5/20058/5/2005APASS
DetailsWilliam E Thomas
Phone #: ###-#### Internet Inspection Request from: steven sewell
ri ok, survey note- 210.52 recep spacing in bedroom, survey posted on site.
p/s o/h r ok
Electrical Rough-In8/3/20058/4/20058/4/2005AFAIL
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: steven sewell cor. do not cover posted called 300.4 nail plates and 11/4", 210.52(A) outlet spacing new part, old where walls are changed, acces to j tub, 250.102(C) needs #4 bond to nipple, 314.16 box fill, make sure of clearence by upstairs window service drop