Final | 9/8/2005 | 9/8/2005 | 9/8/2005 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Clyde Logan ok to final
|
Final | 9/8/2005 | 9/8/2005 | 9/8/2005 | A | PART |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Clyde Logan need to check gfci in bathrooms only. rest ok.
|
Electrical Rough-In | 8/10/2005 | 8/11/2005 | 8/11/2005 | A | CANC |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 8/10/2005 at 12:02:28 PM. see rip
|
Rough-In Permanent Service | 8/11/2005 | 8/11/2005 | 8/11/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 8/10/2005 at 12:02:28 PM. corrections made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 8/9/2005 | 8/10/2005 | 8/10/2005 | A | FAIL |
Bob Reichert
|
|
|
clyde ###-#### called, left message, left corr notice, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, 110.12(C) nm cable jacketing shall not be cut,314.23(C)(1) framing members shall be adequately fastened to each other, 314.23(B) boxes shall be rigidly supported, note to contr on job id sticker has wrong permit number on it
|