Final | 8/10/2005 | 8/11/2005 | 8/11/2005 | A | PASS |
Bob Reichert
|
|
|
reinspection on A/C unit Internet Inspection Request from: Andy Rose corr made, clled contr to cover, ok to final
|
Final | 8/9/2005 | 8/10/2005 | 8/10/2005 | A | FAIL |
Bob Reichert
|
|
|
andy ###-#### called, left message, left corr notice, 300.5, and BCC conduit shall be min 6" deep and exposed for inspection, 342.42(A) connectors shall be made up tight, 342.30(A) imc shall be supported within 3" of box and conduit termination, 408.4 circuit directory shall be evident for use.
|