Final | 11/22/2005 | 11/22/2005 | 11/22/2005 | P | PASS |
Mike Kinnear
|
|
|
cody; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corrections made ok final
|
Final | 11/18/2005 | 11/21/2005 | 11/21/2005 | A | FAIL |
William E Thomas
|
|
|
call cody for garage code. ###-####; Phone #: ###-#### Internet Inspection Request from: Nicole Richardson 1. 410.8C wrong type fixture in closet 2. Must install the fixture in a closet if the closet is wired for fixture.
|
Rough-In Permanent Service | 8/15/2005 | 8/16/2005 | 8/16/2005 | A | PASS |
Bob Reichert
|
|
|
nicole; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corrections made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 8/11/2005 | 8/11/2005 | 8/11/2005 | P | FAIL |
Bob Reichert
|
|
|
steve ###-#### called left message, left corr notice, 250.64(D) gec shall be via tap, not thru panel, 312.5 gec shall have abrasion protection,250.53(G) grd rod shall be flush or below ground, 300.4(A)(1) edge of bored holes shall be 1 1/4" from edge of framing member or use nailplate, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, 210.52 (D) recpt shall be 3'-0" to edge of basin in bathroom, BCC job id sticker shall be posted
|