Permit Information
Permit NumberELE05-02943
StatusFinaled
Name POWERBOUND ELECTRIC INC
Site Address 5394 N BROOK MIST PL
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/22/200511/22/200511/22/2005PPASS
DetailsMike Kinnear
cody; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corrections made ok final
Final11/18/200511/21/200511/21/2005AFAIL
DetailsWilliam E Thomas
call cody for garage code. ###-####; Phone #: ###-#### Internet Inspection Request from: Nicole Richardson
1. 410.8C wrong type fixture in closet
2. Must install the fixture in a closet if the closet is wired for fixture.
Rough-In Permanent Service8/15/20058/16/20058/16/2005APASS
DetailsBob Reichert
nicole; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corrections made, ric ok, p/s u/g n ok
Rough-In Permanent Service8/11/20058/11/20058/11/2005PFAIL
DetailsBob Reichert
steve ###-#### called left message, left corr notice, 250.64(D) gec shall be via tap, not thru panel, 312.5 gec shall have abrasion protection,250.53(G) grd rod shall be flush or below ground, 300.4(A)(1) edge of bored holes shall be 1 1/4" from edge of framing member or use nailplate, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, 210.52 (D) recpt shall be 3'-0" to edge of basin in bathroom, BCC job id sticker shall be posted