Final | 9/19/2005 | 9/20/2005 | 9/20/2005 | A | PASS |
Jack Frank
|
|
|
charlene; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa note house was not wired to meet code, owner complained about correction, persons above me allowed wiring less than 2005 NEC, final by them
|
Final | 9/13/2005 | 9/14/2005 | 9/14/2005 | A | FAIL |
Jack Frank
|
|
|
charlene; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles cor. posted called 314.16 box fill, 314.17 needs connectors where romex enters 1/2 KOs, 250.148 shall terminate all equip grds together in boxes, shall IDwhite wire in 10/2 for WH needs light fixtue or switched outlet for liv rm
|
Final | 9/12/2005 | 9/12/2005 | 9/12/2005 | P | NH |
Jack Frank
|
|
|
or ###-#### ; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called both numbers
|
Electrical Rough-In | 8/12/2005 | 8/12/2005 | 8/12/2005 | A | FAIL |
Jack Frank
|
|
|
cor. posted met owner, needs 2 grd rods bond hot and cold, 312.5(A&C) conn for cables, they rewired house, need to wire it too 2005 NEC
|
Rough-In Permanent Service | 8/11/2005 | 8/12/2005 | 8/12/2005 | A | PASS |
Jack Frank
|
|
|
charlene ###-#### r/i failed see added r/i p/s o/h rec. ok jf
|