Final | 9/6/2005 | 9/6/2005 | 9/6/2005 | P | PASS |
Jack Frank
|
|
|
dan ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok
|
Final | 8/30/2005 | 8/30/2005 | 8/30/2005 | P | FAIL |
Jack Frank
|
|
|
shane; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles cor. posted called 210.8 needs gfci for recepts in shop, 210.70 needs outside light, 250.24 terminate GEC to neutral bus,and install bond screw, 300.4(D) shall provide 11/4" for MC cable
|
Electrical Rough-In | 8/29/2005 | 8/29/2005 | 8/29/2005 | P | PASS |
Bob Reichert
|
|
|
shane; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover trench, told contr to add one more gnd rod and to color white wire on 20A ,240v ckt and to call for final
|