Temporary Service | 8/29/2005 | 8/30/2005 | 8/30/2005 | A | PASS |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas T/S O/H Ok
|
Temporary Service | 8/26/2005 | 8/26/2005 | 8/26/2005 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas 404.8 center of breaker handle shall be max 6'-7" above floor, 312.5 all conductors entering enclosure shall have abrasion protection,250.92(A) metal parts of service equipment shall be bonded,408.4 circuit directory shall be provided, re-inspection fee due,called contr, left corr notice
|
Temporary Service | 8/22/2005 | 8/22/2005 | 8/22/2005 | P | CANC |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas Inspection cancelled from web by: Joe Thomas
|