Temporary Service | 8/25/2005 | 8/26/2005 | 8/26/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 8/25/2005 at 1:26:16 PM. Contact: ###-####. corr made, t/s o/h n ok
|
Temporary Service | 8/24/2005 | 8/25/2005 | 8/25/2005 | A | FAIL |
Bob Reichert
|
|
|
stu ###-#### called contr, left corr notice, fee due, 590.6(B)(1) gfci protection shall be provided for recpts,408.4 circuit directory shall be provided, 312.5 abrasion protection shall be provided for gec, BCC job id sticker shall be posted
|