Final | 9/23/2005 | 9/26/2005 | 9/26/2005 | A | PASS |
Bob Reichert
|
|
|
trent; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa signed occ card, ok to final
|
Rough-In Permanent Service | 9/1/2005 | 9/2/2005 | 9/2/2005 | P | PASS |
Bob Reichert
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ric ok p/s meter bank existing n ok
|
Electrical Rough-In | 9/1/2005 | 9/1/2005 | 9/1/2005 | P | FAIL |
Bob Reichert
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa callede contr, left corr notice, 330.30(B) mc cable shall be supported within 12" of box, 110.22 identification shall be provided for service, bldg space, and sub-panel,110.26(A)(2),(3) work space and height shall be provided for a/c equip.
|