Final | 2/9/2006 | 2/10/2006 | 2/10/2006 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters correction made, signed struct card, ok to final
|
Final | 2/7/2006 | 2/7/2006 | 2/7/2006 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters called contr, bldr, left corr notice, 110.26(A)(1) depth of working space shall be 3' in front of panel. no cards available for occupancy.
|
Final | 2/7/2006 | 2/7/2006 | 2/7/2006 | A | NR |
Bob Reichert
|
|
|
Spoke to Bob Reichart last Thursday concerning lights on Niblett side of building. Factory miship on the lighting and they will use floor lighting until lights can be reshipped.; Phone #: ###-#### Internet Inspection Request from: Celinda Winters called contr about permit, water heater, and panel space. told to recall for final
|
Electrical Rough-In | 11/15/2005 | 11/15/2005 | 11/15/2005 | P | PASS |
Bob Reichert
|
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles soffits and recessed lighting ok to cover, ceiling ok to cover
|
Electrical Rough-In | 11/4/2005 | 11/7/2005 | 11/7/2005 | A | CANC |
Bob Reichert
|
|
|
see rip
|
Rough-In Permanent Service | 11/7/2005 | 11/7/2005 | 11/7/2005 | P | PASS |
Bob Reichert
|
|
|
ri walls only ok, p/s u/g n ok
|
Electrical Rough-In | 11/3/2005 | 11/3/2005 | 11/3/2005 | P | CANC |
Bob Reichert
|
|
|
Need partial so structural can approve the building for cover. We are waiting for can lights to ship into town. All wiring is installed we are just waiting for the lights. The General Contractor has contacted the structural Inspector and he said if you give a partial rough-in they can start installing the exterior dryvit. Please call Brandon for any questions; Phone #: ###-#### Internet Inspection Request from: Celinda Winters called contr, told him this permit no. was used for t/s, and bldg permit states that each tenant space needs an indidual permit.
|
Temporary Service | 9/12/2005 | 9/12/2005 | 9/12/2005 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters t/s u/g re-use existing temp pole, ok
|