Final | 11/9/2005 | 11/10/2005 | 11/10/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 11/9/2005 at 3:15:34 PM. Contact: ###-####. called contr, ok to final
|
Rough-In Permanent Service | 9/22/2005 | 9/23/2005 | 9/23/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/22/2005 at 4:29:26 PM. Contact: ###-####. corr made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 9/20/2005 | 9/22/2005 | 9/22/2005 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/20/2005 at 4:20:06 PM. Contact: ###-####. called contr, left corr notice, left message,312.5 conductors entering enclosures shall have abrasion protection, 408.38 panel shall be dead front, 300.4(D) 1 1/4" shall be maintained from edge of framing members
|