Electrical Rough-In | 10/21/2005 | 10/21/2005 | 10/21/2005 | P | PASS |
William E Thomas
|
|
|
michael; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ri ok
|
Electrical Rough-In | 10/19/2005 | 10/20/2005 | 10/20/2005 | P | FAIL |
Bob Reichert
|
|
|
lila or mike; Phone #: ###-#### Internet Inspection Request from: Barbara Moore BCC all make-up shall be done (Ground Wires), 210.52(A) recpt shall be added behind bookcase, 250.80 metal boxes shall be grounded, 312.5 conductors entering boxes shall have abrasion protection, 314.17(C) nm cable shall be stapled within 8" of box,300.4(A) bored hole edge shall be 1 1/4" from edge,300.4(D) nm cable shall be 1 1/4" from edge of framing member, met owner and reviewed, left correction notice, said to recall.
|
Electrical Rough-In | 10/14/2005 | 10/17/2005 | 10/17/2005 | A | CANC |
William E Thomas
|
|
|
cramer; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
Conference | 10/17/2005 | 10/17/2005 | 10/17/2005 | P | DONE |
William E Thomas
|
|
|
cramer; Phone #: ###-#### Internet Inspection Request from: Barbara Moore talked with home owner about stapleing, nail plates, 6' 12' rule, make-up, bathroom curcuit.
|