Temporary Service | 9/16/2005 | 9/16/2005 | 9/16/2005 | P | PASS |
Jack Frank
|
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles t/s u/g new ok
|
Temporary Service | 9/15/2005 | 9/15/2005 | 9/15/2005 | P | FAIL |
Bob Reichert
|
|
|
chris ###-#### called contr, left corr notice, fee due for re-inspection, 312.5 conductors entering enclosures shall be protected from abrasion, 250.53(G) rod electrode shall be 8' long and flush or below ground, 110.12(C) there shall be no broken parts,( 50a recpt and gec), 110.26(A)(1) work space shall be provided,BCC job id sticker shall be posted, address shall be posted
|