Temporary Service | 9/16/2005 | 9/16/2005 | 9/16/2005 | P | PASS |
Jack Frank
|
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles t/s u/g new ok
|
Temporary Service | 9/15/2005 | 9/15/2005 | 9/15/2005 | P | FAIL |
Bob Reichert
|
|
|
chris ###-#### called contr, left corr notice, 250.24(C) grounded conductor shall be run to service disconnect and bonded, 200.7 grounded conductor shall be identified by color,312.5 conductors entering enclosures shall be protected from abrasion, 250.53(G) rod electrode shall be 8' long and flush or below ground, BCC job id sticker shall be posted, address shall be posted. re-inspection fee due.
|