Temporary Service | 9/27/2005 | 9/28/2005 | 9/28/2005 | A | PASS |
Bob Reichert
|
|
|
###-#### - nicole corrections made, t/s u/g n ok
|
Temporary Service | 9/21/2005 | 9/21/2005 | 9/21/2005 | P | FAIL |
Bob Reichert
|
|
|
please re-inspect. corrections have been made to pole. Thank you; Phone #: ###-#### Internet Inspection Request from: Nicole BCC Job ID sticker shall be posted, erosion control signs posted, 250.56 a single electrode shall be augmented by one additional electrode not less than 6' apart, 250.146 Equipment bonding jumper shall be used to connect the gnd terminal of the recpts to the grounded panel, called contr, left corr notice, fee due
|
Temporary Service | 9/15/2005 | 9/16/2005 | 9/16/2005 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Nicole Richardson called contr, left corr notice, re-inspection fee due, BCC job id sticker shall be posted,address shall be posted, 250.52(A)(5) rod gnd electrode shall be 8' long,250.56 shall augment first rod with second gnd rod, 408.7 unused openings shall be closed, 312.5 abrasion protection shall be provided forconductors entering enclosure, 250.24(A)(1) gec shall terminate on same bus as grounded conductor
|