Final | 10/12/2005 | 10/13/2005 | 10/13/2005 | A | PASS |
Bob Reichert
|
|
|
tom; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles owner will put on blank cover and recpt cover. rest ok, corrections made. ok to final
|
Final | 10/3/2005 | 10/4/2005 | 10/4/2005 | P | NR |
Bob Reichert
|
|
|
paul; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, 410.30(C) cord conn fixtures shall be terminated in gnd type plug, 408.4 panel schedule shall be done, 110.3(A) recpt shall not have open neutral,358.30(A),(B) emt shall be strapped within 3' and every 10'
|