Final | 12/2/2005 | 12/5/2005 | 12/5/2005 | A | PASS |
Jack Frank
|
|
|
Garage code 2010.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs ok
|
Final | 12/1/2005 | 12/2/2005 | 12/2/2005 | A | FAIL |
Jack Frank
|
|
|
Garage code - 2010.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs cor fee due posted called left message 213.22 flex not long enough to allow required access to box, 314.16 b0x fill MB bath also 250.148 grd boxes 210.52(A) outlet spacing MB N wall, is outside paddle fan listed for wet location ? need proof
|
Rough-In Permanent Service | 9/26/2005 | 9/26/2005 | 9/26/2005 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs r/i ok p/s o/h new ok
|
Rough-In Permanent Service | 9/23/2005 | 9/23/2005 | 9/23/2005 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs called, left message, left corr notice, first corr notice not complete,314.17(C) nm cable shall be fastened within 8" of box, 312.5 abrasion protection shall be provided for conductors entering enclosures
|
Rough-In Permanent Service | 9/21/2005 | 9/22/2005 | 9/22/2005 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs cor. , do not cover posted called, 300.4 nail plates and 11/4" 210.52 needs outlets in great rm and kit for wall space, install all boxes floor box and boxes in M bath
|